|
The evaluation of bridge design or rehabilitation
options depends partly on a range of restrictions and variables,
most of which are a function of the site. This is particularly
true in an urban environment. For instance, in a bridge type
study, the choices can include bridge vs. tunnel, and fixed
bridge vs. movable bridge. In this situation, it is important
that one bring to the study a full understanding of all these
types of structures. In the case of movable bridges, one must
also be able to evaluate all of the various types and be prepared
to bring innovation to the process.
|
The Hood Canal Bridge connects
the Olympic Peninsula with the Port Gamble area in western Washington
State. The bridge was the world's first floating drawbridge over
tidal waters when completed in 1961. It spans 2.4 km (1.5 miles)
and carries east and westbound lanes of SR 104 traffic over the
Hood Canal. The canal reaches depths of 92 m (300 feet) in places
under the bridge.
The bridge is a floating concrete structure that utilizes a series
of concrete pontoons with two floating draw spans at the center.
The draw spans are designed to provide a 183-m (600-foot) wide opening
for navigation. They divide the bridge into eastern and western
halves.
In 1979, a severe winter storm destroyed the western half of the
bridge. It was replaced in 1982 with a new design, as described
in "The Hood Canal Floating Bridge" by Mike Abrahams.
In 1985, the control system was partially retrofitted with a programmable
logic controller (PLC) and a microwave communication link to the
eastern structure control system to provide wireless communication
between the control systems for the eastern and western structures.
Both structures
have independent electrical power sources, power distribution systems
and control systems.
Inspection Identifies Anomalies
When PB inspected the western structure control system recently,
we noticed two apparent anomalies:
- The presence of 60 volts a.c. on the western
structure longitudinal lock control circuit and motor feeders.
The feeder circuit breakers were open and the feeders should have
been at zero volts.
- The presence of 220 volts a.c. to ground
and 53 volts a.c. to ground on the legs of the main control circuit.
The voltage expected on this circuit was a balanced 120 volts
a.c. to ground, and 240 volts a.c. leg-to-leg.
We were retained subsequently to
conduct a study of the western structure control system. Our aim
was to identify anomalies that were noticed during the preceding
inspection and to develop a plan for corrective action that would
make the control system acceptable for continued service. We conducted
the study in March 1999, with the assistance of maintenance personnel
from the Washington Department of Transportation (WSDOT).
Approach
The fundamental concern with a 240-volt a.c. ungrounded control
system is that a conductor fault to ground will go undetected. If
a ground fault occurs in a 120-volt a.c. grounded system, a high
current will flow to ground and trip the circuit breaker or blow
the fuse. In an ungrounded system, a fault to bridge steel (structural
members, concrete reinforcement bars, conduit and guardrails) can
put voltage on the steel without any current and can go undetected
indefinitely. Bridge steel that has been faulted to presents a shock
hazard to personnel. If a second fault to the bridge steel occurs,
then motors, valves, gates and relays can operate unexpectedly.
The present National Electric Code (NEC) 1999 restricts the use
of ungrounded control systems for these reasons. [Ed. note: See
discussion of the Evergreen Point Bridge in "Bridge
Electrical Inspections" by Bert Crouthamel and others for
an example of a failure in an ungrounded system.]
In certain applications, NEC will permit the use of ungrounded control
systems with proper ground fault monitoring. These applications
are those that must be fault tolerant as opposed to fail-safe, such
as a fire water pump. A single fault to ground would be detected
and alarmed, but the pump circuit breaker would not trip and would
allow the pump to operate. The reason for this exception is that
during a fire it is likely for a conductor to fault but the fire
is the greater risk. Ungrounded control systems are rarely used
outside of power plants, critical industrial processes and fire
protection systems.
Another concern was that separate voltage sources superimposed and
the 220-volt a.c. leg could cause unintended operations. We isolated
the control system circuits methodically to determine if independent
voltage sources were having an additive effect. Test measurements
of voltage, current and resistance were made under various states
of operation and rest. Control circuit continuity was tested and
wiring was traced to verify the system schematics. Paths for induced
voltages were studied and isolated, and circuits were tested to
determine if any ground faults were present.
The main control circuit feeder conductors were measured to ground
with results showing high ohm values. This result indicated there
were no direct faults to ground. The main control transformer (T1)
was tested to verify that it was operating properly. All testing
was performed with the control system communications link to the
east structure off and with critical motor starter circuit breakers
open.
Control System Standards
It is necessary to determine what constitutes an acceptable risk
when engineering movable bridge control systems. The American Association
of State Highway and Transportation Officials (AASHTO) code offers
some guidance, but AASHTO specifications and recommendations are
limited in regards to control systems.
AASHTO specifies that motor and machine brakes for movable bridges
must have fail-safe controls. Unfortunately, these specifications
mention only a preference for grounded controls system and fall
short of mentioning specific fail-safe control system requirements.
Control system standards established for equipment similar to that
found on movable bridges are being used with success.
It is a widely recognized essential requirement that a single electrical
or control system fault should not cause unintended operations.
Most control system standards require designs in which two faults
will not cause unintended operations. Some standards require a control
system that is fault tolerant while being fail-safe as well. Generally,
it is not acceptable for a movable bridge control system to have
two faults cause an unintended operation.

Figure 1: Unused wires were abandoned in place. |
Control
System Description
The control system for the western structure was originally a single
phase, 60 Hz, 240-volt a.c., ungrounded, hardwired relay system.
The 1985 partial retrofit included the addition of a PLC and a microwave
communication link to the eastern structure control system. The
present control system evolved into a hybrid of hardwired relays
and PLC with unused wires abandoned in place (Figure 1). The control
voltage remains 240-volt a.c. ungrounded for the relays and PLC
outputs (Figure 2 on the following page). The PLC inputs use 120
volts a.c. power with a grounded neutral. The PLC addition was designed
to allow operations of eastern and western draw spans from either
the western control room or
the eastern control room without needing a submarine cable. The
western control system includes:
- A control desk in the western tower control
room
- Two hard wired relay panels in the western
tower
- A PLC cabinet.
The control system power originates
at a 20-amp circuit breaker. The breaker serves 480-volt a.c. single-phase
power to the main control transformer (T1). The transformer secondary
supplies 240 volts a.c. power to the control circuits. A lighting
panel provides 120 volts a.c. to an uninterruptible power supply
(UPS) that serves the PLC processor and input modules. The lighting
panel also powers the public address system.

Figure 2: Hood Canal Bridge, West Control System Study Sketch |
Findings
Fault Analysis. There were three basic types of control system
faults to consider with this system:
- Conductor fault to bridge steel, a panel
enclosure or other common ground point
- Conductor fault to another conductor (this
type of fault is rare, but could result in an energized conductor
touching an otherwise de-energized conductor and establishing
a circuit)
- Fault at the PLC's 240 volts a.c. triac outputs.
A conductor-to-conductor fault
is rare but not impossible. We recommended that maintenance be performed
routinely to torque all electrical terminals to avoid loose wires.
This is especially important because the west structure control
panels are on the south flanking pontoon and are constantly exposed
to heavy cyclical vibration caused by waves. The prevailing south
winds frequently cause large waves in the Hood Canal. Roadway traffic
induced vibration was an additional cause for concern.
Triacs tend to fail in the short circuit mode. Such a failure can
be intermittent, making it difficult to detect. The failure would
operate any device connected to the output.
In addition, the entire PLC cabinet and contents were at risk of
a common mode fault. The UPS battery bank was located on top of
the PLC cabinet. A battery acid leak could have resulted in many
possible combinations of open and shorted control circuits. Furthermore,
off gas from overcharging batteries presented an explosion hazard
in the electrical room.
The western span lift control circuits were less vulnerable to unintended
operation due to faults. It would require two faults to start a
hydraulic lift pump and a third fault to energize a lift solenoid
valve. It would take extreme conditions for three faults to occur
coincidentally. One common mode fault might be heavy roadway traffic
or severe winter storms vibrating control wires loose from the terminals.
Another common mode fault could be an animal chewing through a wire
bundle. It was possible for two of the faults to occur over time
and go undetected until the third fault occurs.
Longitudinal Span Locks: Unintended Operations.
Two longitudinal locks couple the eastern and western draw spans.
The locks are hydraulically operated and require a maintained fluid
pressure. The pump control circuit is kept energized so the pump
can start automatically if the fluid pressure bleeds down.
We determined that the following scenario could result in the unintended
unlocking of both longitudinal locks in a manner that could go undetected:
The western bridge control circuit that unlocks the
longitudinal locks does not have power to it normally until the
bridge is made ready for an opening. It would take two concurrent
faults to unlock these locks. For example, one of the main control
circuit wires has a back-fed voltage. This back-feed is possible
because of a jumper of unknown origin. The jumper effectively bypasses
a control relay used to ready the control system for operation.
A wire connected to the unlocking solenoid valves could fault to
ground. If any of the main control circuit return wires also fault
to ground, then the ground path could complete a circuit and the
unlocking solenoid valves would energize. This would result in unlocking
the longitudinal locks.
The longitudinal locks have two
levels of mechanical redundancy:
- The presence of two longitudinal locks, although
this redundancy must be discounted because they are both needed
for span alignment and they share a common control circuit
- The presence of the northern and southern end locks in the machine
houses.
The end locks would help to limit
the motion of the western span if the longitudinal locks become
unlocked. The eastern span end locks are not used so the span can
move with the tide. Therefore, the eastern and western spans are
likely to separate if the longitudinal locks become unlocked. We
recommended that the control circuits for longitudinal locks be
modified until the bridge control system could be replaced.
Traffic and Barrier Gates: Unintended Operations. The undetected,
two ground fault scenario is not restricted to the longitudinal
span locks. This condition can occur with any electrically operated
device in this control system. The greatest risk to the users of
the bridge would be the unintended operation of a traffic gate or
the barrier gate while the bridge is open to roadway traffic. The
barrier gate will close if a motor control circuit wire connects
to a main control circuit wire through two ground faults because
a complete circuit will put 240 volts a.c. across the gate motor
starter relay.
A similar situation could occur when the control system is made
ready for an operation. If two ground faults that connect any of
the main control circuit wires to either motor control circuit wire
have occurred, then the barrier gate will close as soon as the traffic
warning light is turned on while the traffic gates are still open.
The western traffic gates will close unintentionally if a single
failure occurs when the western traffic warning signal is turned
"on" from the eastern structure control room. The scenario
is as follows:
A single triac short circuit failure on a specific
PLC output occurs. The output is for the eastern control of western
traffic gates down command. This will energize the gate control
relay just as soon as the western traffic warning signal is turned
on, but only if operating the western structure from the eastern
control room. The gate control relay operates one of two western
traffic gate motor starters.
Two coincident triac short circuit
failures on specific output addresses would cause the northwest
traffic gate to close unintentionally without any operator action.
Similarly, two other coincident triac short circuit failures would
also cause the southwest traffic gate to close. One failure could
go undetected indefinitely until a second failure caused a gate
to close with traffic on the bridge.
Recommendations
We made the following recommendations, which would greatly reduce
the possibility of unintended equipment operations:
- Replace the control system with a grounded,
120-volt a.c. system.
- Replace the hardwired relays and triac outputs
with a PLC using relay type outputs.
- Replace some 240-volt devices with 120-volt equipment, such
as the hydraulic solenoid valves and the motor starter coils.
A grounded control system will
be faster and easier for the client to trouble shoot because there
will be no back-feeding voltages. Any fault to ground will cause
a breaker to trip with a grounded system. The system should be designed
to be fail-safe. Control configuration should be engineered to require
four or more coincidental faults before the longitudinal span locks
or gates can operate unintentionally. For the remaining equipment,
it is acceptable for three coincidental faults to cause unintended
operations, but common mode failures should be minimized. Consideration
should also be given to using vibration proof terminals for all
new wiring.
It will be necessary to keep the bridge operational as long as possible
and minimize down time. Therefore, field wiring replacements must
be minimized and it will be necessary to make some new conduit penetrations.
Any new conduit penetration will require a non-destructive method
for locating reinforcing bars and tendons. Core drilling the floating
concrete pontoons must be done with extreme care.
As a result of our recommendations, the western half of the bridge
is scheduled for a total control system rehabilitation. Interim
safety provisions were made to the bridge operating procedures until
the rehabilitation is completed.
|